CoolSim · Summary Report
Example Data Hall
Simulated September 9, 2026 · CoolSim 5.4 · Fine mesh, 655,782 cells
124.11 × 57.49 × 11.75 ft · 7,135 ft²
Non-raised floor, ceiling return plenum
234 racks in 47 rows · 936 kW IT load · 18 cooling units
Result
Overcooled
Every rack draws in air colder than ASHRAE recommends. None runs hot.
17 of 18 cooling units supply air at 60.0 °F, below the 64.4 °F that ASHRAE recommends at a rack inlet. The other supplies 65.0 °F.
Rack inlets against the ASHRAE recommended range, 64.4–80.6 °F
234
Too cold
coldest inlet below 64.4 °F
0
In range
every inlet point inside the range
0
Too hot
warmest inlet above 80.6 °F

Key indices

Cooling capacity in useCAPACITY
87% Little headroom
0 50 80 100 120
Heat removed by the active cooling units ÷ their rated capacity. Above 100% the model asks more of the units than they are rated for.
Return Temperature IndexRTI
98.6% Balanced
50 70 80 100 120 130 150
BypassRecirculation
Supply air vs. rack demand. 100% = matched; below = cold air bypasses the racks, above = hot air recirculates.
Rack Cooling Index, highRCIHI
100.0% Good
50 90 95 100
100% = no rack inlet above the recommended maximum temperature.
Rack Cooling Index, lowRCILO
28.9% Poor
50 90 95 100
100% = no rack inlet below the recommended minimum temperature.

Findings

Racks234 of 234racks draw some air below the 64.4 °F recommended minimum; 155 are below it on average. Coldest inlet: 60.1 °F at RackRow_16 · Rack_1.
Racks0 of 234racks above the 80.6 °F recommended maximum. Warmest inlet: 76.9 °F at RackRow_39 · Rack_4. All 234 stay inside the allowable 59–90 °F.
Cooling97%of its rating on the busiest cooling unit, CRAC_14_1: 58.0 kW of 60 kW. Across all 18 units: 937 kW of 1,080 kW.
Airflow+1.5%more air supplied than the racks draw: 117,013 cfm supplied, 115,338 cfm through the racks. Little bypass, little recirculation.
EnergyNot computedPUE and annual cooling cost need the cooling system’s COP, which was not entered for this model.
RTI, RCIHI and RCILO are trademarks of ANCIS Inc. · Every rack, cooling unit and grille is listed in the tables below.
Example Data Hall · Summary Report

Racks

234 of 234 racks take in some air colder than the recommended 64.4 °F minimum. None takes in any warmer than the 80.6 °F maximum.

Where: racks are colored only if the air they take in is a risk to the servers

Coldest inletRackRow_16 · Rack_1 · 60.1 °FWarmest inletRackRow_39 · Rack_4 · 76.9 °F17 cooling units supply 60.0 °Fbelow the 64.4 °F recommended minimumCRAC_0_01 supplies 65.0 °Finside the recommended range
Colder than allowable
below 59.0 °F
0 racks
Safe
59.0–80.6 °F
234 racks
Warmer than recommended
80.6–90.0 °F
0 racks
Warmer than allowable
above 90.0 °F
0 racks
The color is the rack’s warmest inlet point, or its coldest when that is the only one outside the range, as in the Rack Cooling Report. Grey is safe: every point inside the ASHRAE allowable range and none warmer than recommended. Server faces are drawn where a rack’s inlet faces this view; cooling units along the near wall are cut off low down so the racks behind them show.

Racks furthest outside the recommended range on average

Rack rowRackColdest inlet
°F
Average inlet
°F
Warmest inlet
°F
Average outside range by
°F
ASHRAE recommended
RackRow_14Rack_160.160.661.03.8Too cold
RackRow_16Rack_160.160.661.13.8Too cold
RackRow_22Rack_160.260.763.23.7Too cold
RackRow_28Rack_1560.260.862.63.6Too cold
RackRow_28Rack_860.460.961.73.5Too cold
RackRow_44Rack_160.260.962.73.5Too cold
RackRow_13Rack_160.160.966.73.5Too cold
RackRow_44Rack_960.461.062.13.4Too cold
RackRow_50Rack_160.261.061.63.4Too cold
RackRow_44Rack_860.461.061.63.4Too cold
224 more racks draw some air outside the range. All 234 racks, with flow rate, power and exit temperature, are in the tables below.

How the air moves

The room's solved airflow. Turn the model, move the slice, and trace air from the cooling units, the rack exhausts, or into the warmest racks.

Appendix

Rack cooling

All racks 234
Rack row Rack Inlet temperature
°F
Mean exit
temperature
°F
Flow rate
cfm
Heat load
kW
Liquid cooling
kW
ASHRAE inlet range
Min Max Mean Recommended1 Allowable1
RackRow_46 Rack_1 60.5 74.1 65.9 91.0 500 4.00 0.00
Too cold
Pass
Rack_2 60.6 74.1 67.3 92.7 495 4.00 0.00
Too cold
Pass
Rack_3 60.6 73.5 67.5 92.9 495 4.00 0.00
Too cold
Pass
Rack_4 60.7 70.5 66.0 91.4 494 4.00 0.00
Too cold
Pass
Rack_5 60.8 67.4 64.5 89.9 492 4.00 0.00
Too cold
Pass
Rack_6 60.7 64.9 62.7 88.1 491 4.00 0.00
Too cold
Pass
Rack_7 60.5 63.2 62.0 87.4 490 4.00 0.00
Too cold
Pass
Rack_8 60.5 64.7 62.9 88.3 491 4.00 0.00
Too cold
Pass
Rack_9 60.4 67.0 64.0 89.4 492 4.00 0.00
Too cold
Pass
Rack_10 60.4 72.5 65.6 91.0 494 4.00 0.00
Too cold
Pass
Rack_11 60.4 76.2 66.9 92.3 495 4.00 0.00
Too cold
Pass
Rack_12 60.4 76.5 66.6 92.0 494 4.00 0.00
Too cold
Pass
Rack_13 60.3 76.7 65.7 91.2 494 4.00 0.00
Too cold
Pass
Rack_14 60.3 74.4 64.1 89.5 492 4.00 0.00
Too cold
Pass
Rack_15 60.3 70.0 62.4 87.9 490 4.00 0.00
Too cold
Pass
RackRow_45 Rack_1 60.3 70.5 63.9 89.0 498 4.00 0.00
Too cold
Pass
Rack_2 60.4 72.2 65.4 90.9 493 4.00 0.00
Too cold
Pass
Rack_3 60.5 72.7 66.3 91.8 494 4.00 0.00
Too cold
Pass
Rack_4 60.6 73.3 66.9 92.3 495 4.00 0.00
Too cold
Pass
Rack_5 60.6 73.3 67.0 92.4 495 4.00 0.00
Too cold
Pass
Rack_6 60.7 71.3 65.4 90.8 493 4.00 0.00
Too cold
Pass
Rack_7 60.7 65.6 62.8 88.3 491 4.00 0.00
Too cold
Pass
Rack_8 60.7 62.5 61.6 87.0 490 4.00 0.00
Too cold
Pass
Rack_9 60.9 67.6 63.6 89.0 492 4.00 0.00
Too cold
Pass
Rack_10 60.9 73.2 66.6 92.1 494 4.00 0.00
Too cold
Pass
Rack_11 60.8 73.2 67.3 92.7 495 4.00 0.00
Too cold
Pass
Rack_12 60.7 71.9 66.5 91.9 494 4.00 0.00
Too cold
Pass
Rack_13 60.6 70.4 65.3 90.7 493 4.00 0.00
Too cold
Pass
Rack_14 60.5 68.4 63.8 89.2 492 4.00 0.00
Too cold
Pass
Rack_15 60.4 65.6 62.6 88.1 491 4.00 0.00
Too cold
Pass
RackRow_44 Rack_1 60.2 62.7 60.9 86.0 495 4.00 0.00
Too cold
Pass
Rack_2 60.2 65.7 61.7 87.1 490 4.00 0.00
Too cold
Pass
Rack_3 60.3 67.0 62.8 88.2 491 4.00 0.00
Too cold
Pass
Rack_4 60.3 66.9 63.2 88.6 491 4.00 0.00
Too cold
Pass
Rack_5 60.4 66.5 63.3 88.7 491 4.00 0.00
Too cold
Pass
Rack_6 60.4 66.3 62.9 88.3 491 4.00 0.00
Too cold
Pass
Rack_7 60.4 63.4 61.9 87.3 490 4.00 0.00
Too cold
Pass
Rack_8 60.4 61.6 61.0 86.4 489 4.00 0.00
Too cold
Pass
Rack_9 60.4 62.1 61.0 86.4 489 4.00 0.00
Too cold
Pass
RackRow_43 Rack_1 60.8 74.6 64.7 89.9 499 4.00 0.00
Too cold
Pass
Rack_2 60.9 74.4 65.9 91.3 494 4.00 0.00
Too cold
Pass
Rack_3 61.0 71.9 65.6 91.1 494 4.00 0.00
Too cold
Pass
Rack_4 61.0 66.8 64.1 89.6 492 4.00 0.00
Too cold
Pass
Rack_5 61.1 65.5 63.3 88.7 491 4.00 0.00
Too cold
Pass
Rack_6 60.4 62.9 61.8 87.2 490 4.00 0.00
Too cold
Pass
Rack_7 60.3 63.1 61.6 87.1 490 4.00 0.00
Too cold
Pass
Rack_8 60.3 64.7 62.5 87.9 491 4.00 0.00
Too cold
Pass
RackRow_42 Rack_1 60.4 75.1 65.5 90.6 499 4.00 0.00
Too cold
Pass
Rack_2 60.5 75.9 67.3 92.7 495 4.00 0.00
Too cold
Pass
Rack_3 60.6 74.7 67.7 93.1 496 4.00 0.00
Too cold
Pass
Rack_4 60.8 74.0 67.2 92.7 495 4.00 0.00
Too cold
Pass
Rack_5 60.9 69.5 65.6 91.0 493 4.00 0.00
Too cold
Pass
Rack_6 61.0 66.3 64.2 89.6 492 4.00 0.00
Too cold
Pass
Rack_7 60.7 64.1 62.4 87.9 491 4.00 0.00
Too cold
Pass
Rack_8 60.6 62.8 61.8 87.2 490 4.00 0.00
Too cold
Pass
RackRow_41 Rack_1 60.2 64.7 61.9 87.0 496 4.00 0.00
Too cold
Pass
Rack_2 60.3 66.1 63.0 88.4 491 4.00 0.00
Too cold
Pass
Rack_3 60.4 66.9 63.8 89.2 492 4.00 0.00
Too cold
Pass
Rack_4 60.5 69.3 64.7 90.1 493 4.00 0.00
Too cold
Pass
Rack_5 60.5 70.0 65.3 90.7 493 4.00 0.00
Too cold
Pass
Rack_6 60.6 68.0 64.0 89.4 492 4.00 0.00
Too cold
Pass
Rack_7 60.6 63.8 61.9 87.3 490 4.00 0.00
Too cold
Pass
Rack_8 60.6 61.5 61.1 86.5 489 4.00 0.00
Too cold
Pass
RackRow_40 Rack_1 60.5 66.3 62.3 87.4 496 4.00 0.00
Too cold
Pass
Rack_2 60.5 65.9 62.4 87.8 490 4.00 0.00
Too cold
Pass
Rack_3 60.5 64.8 62.2 87.7 490 4.00 0.00
Too cold
Pass
Rack_4 60.5 63.8 62.0 87.5 490 4.00 0.00
Too cold
Pass
Rack_5 60.5 63.0 61.9 87.3 490 4.00 0.00
Too cold
Pass
Rack_6 60.5 62.5 61.7 87.1 490 4.00 0.00
Too cold
Pass
Rack_7 60.4 62.3 61.6 87.0 490 4.00 0.00
Too cold
Pass
Rack_8 60.4 62.1 61.5 86.9 490 4.00 0.00
Too cold
Pass
RackRow_39 Rack_1 60.2 73.9 65.2 90.3 499 4.00 0.00
Too cold
Pass
Rack_2 60.2 76.0 65.9 91.3 494 4.00 0.00
Too cold
Pass
Rack_3 60.2 76.5 65.6 91.0 493 4.00 0.00
Too cold
Pass
Rack_4 60.2 76.9 64.7 90.1 493 4.00 0.00
Too cold
Pass
Rack_5 60.2 76.4 63.2 88.6 491 4.00 0.00
Too cold
Pass
Rack_6 60.2 71.2 61.6 87.0 490 4.00 0.00
Too cold
Pass
RackRow_38 Rack_1 60.5 65.8 63.7 88.9 498 4.00 0.00
Too cold
Pass
Rack_2 60.5 70.8 65.3 90.8 493 4.00 0.00
Too cold
Pass
Rack_3 60.4 74.3 66.6 92.0 494 4.00 0.00
Too cold
Pass
Rack_4 60.4 75.2 66.6 92.1 494 4.00 0.00
Too cold
Pass
Rack_5 60.3 75.2 65.6 91.1 494 4.00 0.00
Too cold
Pass
Rack_6 60.3 72.6 63.5 88.9 492 4.00 0.00
Too cold
Pass
RackRow_37 Rack_1 60.8 66.9 63.9 89.0 498 4.00 0.00
Too cold
Pass
Rack_2 60.8 69.5 65.2 90.6 493 4.00 0.00
Too cold
Pass
Rack_3 60.7 68.6 64.4 89.8 492 4.00 0.00
Too cold
Pass
Rack_4 60.6 66.3 63.5 88.9 492 4.00 0.00
Too cold
Pass
Rack_5 60.5 65.1 62.6 88.1 491 4.00 0.00
Too cold
Pass
Rack_6 60.4 63.7 61.9 87.3 490 4.00 0.00
Too cold
Pass
RackRow_36 Rack_1 60.6 66.7 62.3 87.5 496 4.00 0.00
Too cold
Pass
Rack_2 60.6 67.1 63.2 88.6 491 4.00 0.00
Too cold
Pass
Rack_3 60.6 65.6 62.6 88.0 491 4.00 0.00
Too cold
Pass
Rack_4 60.5 63.9 61.9 87.4 490 4.00 0.00
Too cold
Pass
Rack_5 60.4 62.9 61.5 87.0 490 4.00 0.00
Too cold
Pass
Rack_6 60.3 62.2 61.3 86.7 489 4.00 0.00
Too cold
Pass
RackRow_35 Rack_1 60.7 64.7 63.1 88.2 497 4.00 0.00
Too cold
Pass
Rack_2 63.5 64.8 64.1 89.5 492 4.00 0.00
Too cold
Pass
Rack_3 62.9 64.9 63.7 89.2 492 4.00 0.00
Too cold
Pass
Rack_4 62.6 64.9 63.5 88.9 492 4.00 0.00
Too cold
Pass
Rack_5 62.6 64.9 63.5 89.0 492 4.00 0.00
Too cold
Pass
Rack_6 62.6 64.9 63.7 89.1 492 4.00 0.00
Too cold
Pass
RackRow_34 Rack_1 61.6 63.3 62.8 87.9 497 4.00 0.00
Too cold
Pass
Rack_2 61.6 64.2 63.0 88.5 491 4.00 0.00
Too cold
Pass
Rack_3 61.6 66.9 63.7 89.2 491 4.00 0.00
Too cold
Pass
Rack_4 61.6 69.5 64.6 90.0 492 4.00 0.00
Too cold
Pass
Rack_5 61.6 70.0 64.7 90.1 492 4.00 0.00
Too cold
Pass
Rack_6 61.6 68.9 64.3 89.7 493 4.00 0.00
Too cold
Pass
Rack_7 61.5 67.3 64.2 89.6 493 4.00 0.00
Too cold
Pass
Rack_8 61.5 66.6 64.3 89.7 493 4.00 0.00
Too cold
Pass
Rack_9 61.5 66.6 64.6 90.0 493 4.00 0.00
Too cold
Pass
Rack_10 61.4 67.7 64.9 90.3 494 4.00 0.00
Too cold
Pass
Rack_11 61.3 70.0 65.4 90.9 494 4.00 0.00
Too cold
Pass
Rack_12 61.3 72.2 65.9 91.4 495 4.00 0.00
Too cold
Pass
Rack_13 61.2 73.8 66.0 91.4 494 4.00 0.00
Too cold
Pass
Rack_14 61.0 74.1 65.4 90.8 493 4.00 0.00
Too cold
Pass
Rack_15 60.8 73.5 64.2 89.6 492 4.00 0.00
Too cold
Pass
RackRow_33 Rack_1 60.3 71.2 62.9 88.0 497 4.00 0.00
Too cold
Pass
Rack_2 60.3 75.8 65.2 90.6 493 4.00 0.00
Too cold
Pass
Rack_3 60.4 76.5 66.9 92.3 495 4.00 0.00
Too cold
Pass
Rack_4 60.4 75.6 67.0 92.4 495 4.00 0.00
Too cold
Pass
Rack_5 60.5 71.8 66.4 91.8 494 4.00 0.00
Too cold
Pass
Rack_6 60.6 69.0 65.0 90.4 493 4.00 0.00
Too cold
Pass
Rack_7 60.6 66.1 63.2 88.6 491 4.00 0.00
Too cold
Pass
Rack_8 60.9 62.8 61.8 87.2 490 4.00 0.00
Too cold
Pass
Rack_9 61.0 62.8 62.1 87.5 490 4.00 0.00
Too cold
Pass
Rack_10 61.0 64.6 63.1 88.5 491 4.00 0.00
Too cold
Pass
Rack_11 61.0 65.5 63.7 89.1 492 4.00 0.00
Too cold
Pass
Rack_12 61.0 69.4 64.8 90.2 493 4.00 0.00
Too cold
Pass
Rack_13 60.9 73.6 66.3 91.7 494 4.00 0.00
Too cold
Pass
Rack_14 60.8 74.5 66.3 91.7 494 4.00 0.00
Too cold
Pass
Rack_15 60.7 74.3 65.3 90.7 493 4.00 0.00
Too cold
Pass
RackRow_32 Rack_1 60.4 67.4 62.8 87.9 497 4.00 0.00
Too cold
Pass
Rack_2 60.5 72.9 64.8 90.2 493 4.00 0.00
Too cold
Pass
Rack_3 60.6 75.2 67.2 92.6 495 4.00 0.00
Too cold
Pass
Rack_4 60.7 74.8 67.5 92.9 495 4.00 0.00
Too cold
Pass
Rack_5 60.8 69.9 66.2 91.6 494 4.00 0.00
Too cold
Pass
Rack_6 60.8 67.8 64.7 90.1 493 4.00 0.00
Too cold
Pass
Rack_7 60.5 65.2 62.6 88.1 491 4.00 0.00
Too cold
Pass
Rack_8 60.5 62.6 61.8 87.3 490 4.00 0.00
Too cold
Pass
Rack_9 60.4 63.9 62.6 88.0 491 4.00 0.00
Too cold
Pass
Rack_10 60.4 65.8 63.6 89.0 492 4.00 0.00
Too cold
Pass
Rack_11 60.4 67.6 64.4 89.8 492 4.00 0.00
Too cold
Pass
Rack_12 60.3 73.2 66.2 91.7 494 4.00 0.00
Too cold
Pass
Rack_13 60.3 76.1 67.0 92.4 495 4.00 0.00
Too cold
Pass
Rack_14 60.2 76.8 66.3 91.7 494 4.00 0.00
Too cold
Pass
Rack_15 60.2 75.6 64.2 89.6 492 4.00 0.00
Too cold
Pass
RackRow_31 Rack_1 60.3 71.0 63.3 88.4 497 4.00 0.00
Too cold
Pass
Rack_2 60.3 75.3 65.9 91.3 494 4.00 0.00
Too cold
Pass
Rack_3 60.4 75.0 67.0 92.5 495 4.00 0.00
Too cold
Pass
Rack_4 60.4 73.6 66.6 92.0 494 4.00 0.00
Too cold
Pass
Rack_5 60.5 69.2 64.9 90.3 493 4.00 0.00
Too cold
Pass
Rack_6 60.6 65.6 63.7 89.1 492 4.00 0.00
Too cold
Pass
Rack_7 60.6 64.3 62.5 87.9 491 4.00 0.00
Too cold
Pass
Rack_8 60.5 63.2 61.9 87.3 490 4.00 0.00
Too cold
Pass
Rack_9 60.4 65.2 63.2 88.6 491 4.00 0.00
Too cold
Pass
Rack_10 60.4 66.1 64.1 89.5 492 4.00 0.00
Too cold
Pass
Rack_11 60.4 69.5 65.1 90.5 493 4.00 0.00
Too cold
Pass
Rack_12 60.3 75.2 66.5 91.9 494 4.00 0.00
Too cold
Pass
Rack_13 60.3 76.2 66.6 92.0 494 4.00 0.00
Too cold
Pass
Rack_14 60.3 75.7 65.7 91.2 494 4.00 0.00
Too cold
Pass
Rack_15 60.2 73.7 63.8 89.2 492 4.00 0.00
Too cold
Pass
RackRow_30 Rack_1 60.3 71.5 62.8 88.0 497 4.00 0.00
Too cold
Pass
Rack_2 60.3 71.7 64.2 89.6 492 4.00 0.00
Too cold
Pass
Rack_3 60.3 70.2 65.0 90.4 493 4.00 0.00
Too cold
Pass
Rack_4 60.4 69.7 65.4 90.9 493 4.00 0.00
Too cold
Pass
Rack_5 60.4 69.3 65.5 91.0 493 4.00 0.00
Too cold
Pass
Rack_6 60.4 68.3 65.1 90.5 493 4.00 0.00
Too cold
Pass
Rack_7 60.5 66.8 63.8 89.2 492 4.00 0.00
Too cold
Pass
Rack_8 60.5 63.4 61.8 87.2 490 4.00 0.00
Too cold
Pass
Rack_9 60.4 64.4 62.3 87.8 490 4.00 0.00
Too cold
Pass
Rack_10 60.3 67.7 64.4 89.8 492 4.00 0.00
Too cold
Pass
Rack_11 60.3 68.0 65.1 90.5 493 4.00 0.00
Too cold
Pass
Rack_12 60.3 67.4 64.8 90.3 493 4.00 0.00
Too cold
Pass
Rack_13 60.2 68.5 64.7 90.1 493 4.00 0.00
Too cold
Pass
Rack_14 60.2 71.5 64.6 90.0 493 4.00 0.00
Too cold
Pass
Rack_15 60.2 72.2 63.4 88.8 491 4.00 0.00
Too cold
Pass
RackRow_29 Rack_1 60.2 67.6 62.1 87.3 496 4.00 0.00
Too cold
Pass
Rack_2 60.2 67.5 62.8 88.2 491 4.00 0.00
Too cold
Pass
Rack_3 60.2 67.9 63.4 88.8 491 4.00 0.00
Too cold
Pass
Rack_4 60.3 67.9 63.9 89.3 492 4.00 0.00
Too cold
Pass
Rack_5 60.3 67.0 63.6 89.1 492 4.00 0.00
Too cold
Pass
Rack_6 60.3 65.2 63.0 88.4 491 4.00 0.00
Too cold
Pass
Rack_7 60.3 64.2 62.4 87.8 490 4.00 0.00
Too cold
Pass
Rack_8 60.3 62.2 61.2 86.6 489 4.00 0.00
Too cold
Pass
Rack_9 60.2 63.8 61.9 87.3 490 4.00 0.00
Too cold
Pass
Rack_10 60.2 65.7 63.3 88.7 491 4.00 0.00
Too cold
Pass
Rack_11 60.2 66.2 63.6 89.1 492 4.00 0.00
Too cold
Pass
Rack_12 60.1 66.9 63.7 89.1 492 4.00 0.00
Too cold
Pass
Rack_13 60.1 67.0 63.4 88.8 491 4.00 0.00
Too cold
Pass
Rack_14 60.1 67.0 62.8 88.2 491 4.00 0.00
Too cold
Pass
Rack_15 60.1 67.9 62.1 87.5 490 4.00 0.00
Too cold
Pass
RackRow_28 Rack_1 60.3 63.1 61.2 86.3 495 4.00 0.00
Too cold
Pass
Rack_2 60.3 65.5 61.6 87.1 490 4.00 0.00
Too cold
Pass
Rack_3 60.4 65.4 62.1 87.5 490 4.00 0.00
Too cold
Pass
Rack_4 60.4 65.5 62.4 87.8 491 4.00 0.00
Too cold
Pass
Rack_5 60.4 65.5 62.7 88.1 491 4.00 0.00
Too cold
Pass
Rack_6 60.4 65.4 62.5 88.0 491 4.00 0.00
Too cold
Pass
Rack_7 60.4 64.3 61.6 87.1 490 4.00 0.00
Too cold
Pass
Rack_8 60.4 61.7 60.9 86.3 489 4.00 0.00
Too cold
Pass
Rack_9 60.3 62.8 61.4 86.8 490 4.00 0.00
Too cold
Pass
Rack_10 60.3 64.6 62.3 87.8 490 4.00 0.00
Too cold
Pass
Rack_11 60.3 65.7 62.7 88.2 491 4.00 0.00
Too cold
Pass
Rack_12 60.2 66.2 62.7 88.1 491 4.00 0.00
Too cold
Pass
Rack_13 60.2 66.2 62.3 87.7 490 4.00 0.00
Too cold
Pass
Rack_14 60.2 65.5 61.5 86.9 490 4.00 0.00
Too cold
Pass
Rack_15 60.2 62.6 60.8 86.2 489 4.00 0.00
Too cold
Pass
RackRow_27 Rack_1 60.2 62.5 61.1 86.2 495 4.00 0.00
Too cold
Pass
RackRow_26 Rack_1 60.2 66.5 62.1 87.2 496 4.00 0.00
Too cold
Pass
RackRow_25 Rack_1 60.3 70.6 63.1 88.3 497 4.00 0.00
Too cold
Pass
RackRow_24 Rack_1 60.4 71.0 63.5 88.6 497 4.00 0.00
Too cold
Pass
RackRow_23 Rack_1 60.7 70.7 62.8 87.9 497 4.00 0.00
Too cold
Pass
RackRow_22 Rack_1 60.2 63.2 60.7 85.9 495 4.00 0.00
Too cold
Pass
RackRow_21 Rack_1 60.2 63.5 61.6 86.7 496 4.00 0.00
Too cold
Pass
RackRow_20 Rack_1 60.2 65.9 61.6 86.8 496 4.00 0.00
Too cold
Pass
RackRow_19 Rack_1 60.3 63.7 62.0 87.1 496 4.00 0.00
Too cold
Pass
RackRow_18 Rack_1 60.3 62.5 61.5 86.7 496 4.00 0.00
Too cold
Pass
RackRow_17 Rack_1 60.2 61.7 61.1 86.3 495 4.00 0.00
Too cold
Pass
RackRow_16 Rack_1 60.1 61.1 60.6 85.8 495 4.00 0.00
Too cold
Pass
RackRow_15 Rack_1 60.5 65.2 61.7 86.8 496 4.00 0.00
Too cold
Pass
RackRow_14 Rack_1 60.1 61.0 60.6 85.7 495 4.00 0.00
Too cold
Pass
RackRow_13 Rack_1 60.1 66.7 60.9 86.1 495 4.00 0.00
Too cold
Pass
RackRow_12 Rack_1 60.1 67.1 61.4 86.6 495 4.00 0.00
Too cold
Pass
RackRow_11 Rack_1 60.2 67.0 61.9 87.0 496 4.00 0.00
Too cold
Pass
RackRow_10 Rack_1 60.1 69.0 61.8 86.9 496 4.00 0.00
Too cold
Pass
RackRow_9 Rack_1 60.6 72.6 63.2 88.3 497 4.00 0.00
Too cold
Pass
RackRow_8 Rack_1 60.6 69.9 62.7 87.8 497 4.00 0.00
Too cold
Pass
RackRow_7 Rack_1 60.7 63.1 62.5 87.6 496 4.00 0.00
Too cold
Pass
RackRow_6 Rack_1 60.2 64.8 61.4 86.5 495 4.00 0.00
Too cold
Pass
RackRow_5 Rack_1 60.3 64.0 61.8 86.9 496 4.00 0.00
Too cold
Pass
RackRow_47 Rack_1 60.2 64.3 61.7 86.8 496 4.00 0.00
Too cold
Pass
RackRow_48 Rack_1 60.3 65.4 61.7 86.9 496 4.00 0.00
Too cold
Pass
RackRow_49 Rack_1 60.2 66.5 61.3 86.4 495 4.00 0.00
Too cold
Pass
RackRow_50 Rack_1 60.2 61.6 61.0 86.1 495 4.00 0.00
Too cold
Pass
RackRow_51 Rack_1 62.9 65.0 64.1 89.2 498 4.00 0.00
Too cold
Pass
Total 115,338 936.00 0.00

1 ASHRAE 2008 inlet temperature for class 1 servers: recommended 64.4 to 80.6 °F, allowable 59.0 to 90.0 °F. A rack passes when its coldest and warmest inlet readings are both inside the range.

Red rows: racks whose warmest inlet is above the recommended maximum. Blue rows: racks whose coldest inlet is below the recommended minimum. A rack with both is red.

Heat rejected by liquid cooling0.00 kW
Share of rack heat rejected by liquid cooling0.0%

Cooling units

All cooling units 18
Type CRAC Mean return
temperature
°F
Mean supply
temperature
°F
Supply flow
cfm
Static pressure
in H2O
Heat removal
kW
Deviation from mean1
%
Down Flow CRAC_17_1 86.8 60.0 6,501 0.0194 56.14 7.9
CRAC_16_1 86.8 60.0 6,501 0.0181 56.15 7.9
CRAC_15_1 86.8 60.0 6,501 0.0199 56.26 8.1
CRAC_14_1 87.7 60.0 6,501 0.0198 58.03 11.5
CRAC_13_1 86.6 60.0 6,501 0.0227 55.73 7.1
CRAC_12_1 84.5 60.0 6,501 0.0217 51.30 −1.4
CRAC_11_1 82.3 60.0 6,501 0.0260 46.70 −10.3
CRAC_10_1 82.0 60.0 6,501 0.0253 46.07 −11.5
CRAC_9_1 84.1 60.0 6,501 0.0255 50.56 −2.9
CRAC_8_1 85.2 60.0 6,501 0.0198 52.82 1.5
CRAC_7_1 86.3 60.0 6,501 0.0194 55.16 6.0
CRAC_6_1 87.1 60.0 6,501 0.0181 56.82 9.2
CRAC_5_1 86.9 60.0 6,501 0.0183 56.31 8.2
CRAC_4_1 86.3 60.0 6,501 0.0186 55.09 5.8
CRAC_3_1 84.5 60.0 6,501 0.0212 51.33 −1.4
CRAC_2_1 82.2 60.0 6,501 0.0265 46.59 −10.5
CRAC_1_1 82.3 60.0 6,501 0.0247 46.85 −10.0
CRAC_0_01 83.8 65.0 6,501 0.0272 39.05 −25.0
Total 117,013 936.96
Mean 85.1 60.3 6,501 52.05

1 (unit heat removal − mean heat removal) ÷ mean heat removal.

Room mean pressure: −0.0032 in H2O.

Heat removal in red is more than the unit’s rated cooling capacity.

Energy

COP
not entered
coefficient of performance, as entered
PUE
n/a
power usage effectiveness
DCiE
n/a%
data center infrastructure efficiency
Total facility power
n/a kW
RTI1
98.6%
return temperature index
RCIHI1
100.0%
rack cooling index, high side
RCILO1
28.9%
rack cooling index, low side
Annual operating cost
n/a

1 RTI and RCI are trademarks of ANCIS Inc.

No COP was entered before the run, so PUE, DCiE, facility power and operating cost are not worked out here. The energy calculator works them out from a COP you enter.

Energy calculator

Try other figures here. The run’s figures stay as they are.

COP
PUE
DCiE%
Total facility power W
Annual operating cost

Ceiling grilles

Grille Open area
%
Mean temperature
°F
Flow rate1
cfm
Grille_0 50 82.7 19,943
Grille_1 50 83.7 19,301
Grille_2 50 85.8 17,277
Grille_3 50 87.3 16,932
Grille_4 50 87.2 16,359
Grille_5 50 87.4 16,890
Grille_6 50 86.7 16,026
Total 122,729

1 A negative flow comes into the room from the ceiling plenum.

Model and room

Simulation
ModelExample Data Hall
SimulatedSeptember 9, 2026
Mesh densityFine
Mesh cells655,782
CPUs1
Room
LayoutNon-raised Floor with Ceiling Plenum
Dimensions124.11 × 57.49 × 11.75 ft
Floor area7,134.9 ft²
Return plenum height1.75 ft
CRAC units
Count18
Total supply flow117,013 cfm
Total heat removed936.96 kW
Racks
Rows47
Count234
Total flow115,338 cfm
Total heat load936.00 kW
Ceiling grilles
Count7