Predicting and Optimizing Thermal Performance in Hyperscale Data Center Design
This webinar covers computational fluid dynamics (CFD) modeling of hyperscale, air-cooled data halls: large, repeating pods of racks with hot aisle containment and fan walls. It is aimed at design engineers who need to model leakage, test cooling failures, and read the results.
What the webinar covers
The presenter first defines hot aisle and cold aisle containment and explains why separating hot and cold air raises efficiency. The presenter argues that CFD is mainly for corner cases: losing a cooling unit, adding IT load, or running hot. Return Temperature Index (RTI) and Rack Cooling Index (RCI) are introduced, with a reminder of Bernoulli’s equation to explain why fast air has low static pressure. A short exchange covers whether RTI can be too low.
Next comes the anatomy of a rack: server slots, rails, blanking panels, and the gaps where air leaks. Three levels of leakage detail are compared:
- Leakage spread across the whole containment surface with a baffle.
- Containment sealed except at its intersection with the racks.
- Slightly narrower racks with gaps and a leakage surface that stands in for the rails, the top and the bottom.
The live build in CoolSim sets up a pod with a rack editor, a gap setting, reversed airflow on the opposite row, end caps with leakage off, cloning, grouping, and repeating the pod.
The results section walks through four runs of one model, using a shared report link. It covers the energy report, rack inlet compliance, velocity, leakage slices, pressure and pathlines. Further examples show a single-sided supply layout and a deliberately narrow hot aisle.
Key points
- Hyperscale mostly means large and repeated, so one detailed pod can be grouped and cloned.
- The presenter uses about 125 cubic feet per minute (CFM) per kilowatt for air-cooled equipment. At the rack loads discussed, this is why non-raised-floor fan wall layouts replace raised floors.
- The presenter sees about 40 kW per rack of air cooling as roughly the practical upper limit, and offers this as a personal opinion.
- Too much air wastes energy but does not harm IT equipment. Too little air causes hot spots.
- In the example, supply fell short of rack demand, RTI exceeded 100, and the worst racks sat at the edges where air velocity is high.
- Opposing high-velocity streams meeting in a hot aisle raise static pressure there and push air back through rack rails. A narrow aisle makes this worse.
- Doors are rarely worth modeling. Rails, the top and the bottom are what leak.
- Cheap blanking material, sealing under racks and tightening rack rails are implementation details that decide performance.
- Test N+1 and N+2 cooling failures in more than one configuration.
- Aim for a mesh near a million cells so pathlines are dense enough to read.