Quantifying the Benefits of Data Center Improvements
This webinar shows how to turn computational fluid dynamics (CFD) results into a first-pass estimate of operating savings from a design change. The example adds cold aisle containment to a raised floor data hall, and the talk is aimed at engineers who are asked what a change is worth.
What the webinar covers
The presenter begins with the idea that every data hall has an operating point where energy is lowest, and that a steady-state CFD model can help find it. The talk reviews air management, recirculation and bypass, and the goals of high supply temperature and low airflow. Return Temperature Index (RTI) and Rack Cooling Index (RCI) are defined, with guidance on model detail: start with average watts per rack and add detail only if it changes the answer.
The base model is a raised floor hall with perimeter cooling units, perforated tiles and no containment. CoolSim results show:
- Tile flows that vary with their distance from the cooling units.
- An RTI near 66, meaning the cooling units deliver far more air than the racks need.
- Recirculation visible in pathlines.
- A reported Power Usage Effectiveness (PUE) of about 1.68.
The energy calculation is done in a spreadsheet. It adds IT load, the fan power of the air handlers, and the heat-rejection energy, with the heat-rejection cost set by a coefficient of performance (COP) that the user enters. The presenter notes that fan power has to be paid for twice, once to run the fans and once to remove the heat they add.
The improved case adds cold aisle containment with a small amount of leakage at the rack interface. Airflow drops, supply temperature rises, RTI moves to about 98, and RCI high reaches about 96. The talk closes by turning the energy difference into dollars per year.
Key points
- The presenter’s rule of thumb is roughly 3.5% better chiller efficiency for each 1.8 °F rise in return temperature, and calls it coarse and non-linear in practice.
- In the example, COP was raised from 2.8 to about 3.16 using that rule.
- Fan power varies with the cube of airflow, so a modest cut in airflow gives a large fan saving.
- Containment let supply temperature rise from 68 °F to about 71.6 °F, with return temperature near 92.6 °F.
- The presenter estimates savings of about 300 kW, or roughly half a million dollars a year at 20 cents per kilowatt-hour, assuming a constant electricity price.
- The presenter stresses that the method shows how to approach the question, not a full energy prediction. Weather, economizers and variable-speed equipment change the COP over a year.
- Liquid-cooled sites still need air management for the heat the liquid does not remove, in the presenter’s view.