Raised vs. Non-Raised Floor Data Center Design
This webinar compares raised floor and non-raised (slab) data hall designs from an air management point of view, using computational fluid dynamics (CFD) models built in CoolSim. It is aimed at engineers who design, review or operate contained data halls and want to see where each layout runs into trouble.
What the webinar covers
The presenter starts with what matters when modeling air delivery: the size and placement of the supply outlet, the mass flow rate, and the supply air temperature. The presenter argues that cooling capacity is rarely the limiting factor, because it is simple arithmetic to size. The problem is getting air to the right place. The talk also reviews how total pressure splits into static and dynamic pressure, and why fast-moving air lowers the static pressure that keeps containment working.
The first model is a slab design with ceiling-mounted air handlers, hot aisle containment and a ceiling return plenum. Leakage is built into it with zero-thickness baffles: closed containment walls, rack rails set to leak, and open rack backs. The results show leakage through the rack rails near the high-velocity end of the aisle, where the hot aisle pressure beats the cold aisle pressure. The same room is then rerun with a four-foot floor plenum and perforated tiles. Its weak spot moves to the far end of the plenum, but the tiles let an operator bias airflow toward it.
A larger slab design with a parametric study (four variations at once) turns off one air handler in an N+1 layout. Part of the room is starved of air, and racks close to the air handlers see very high aisle velocities. A third design places fan coil units on the walls. Air leaks into the containment before it reaches the middle of the room, and putting a floor plenum under the same layout gives a better and more manageable result. The session closes with audience questions on underfloor obstructions, default airflow per kilowatt, server fans and tile load ratings.
Key points
- Air delivery, not cooling capacity, is the usual constraint in contained halls. Supply outlet size and placement, flow rate and supply temperature are the inputs that matter most.
- Fast air moving along an aisle lowers static pressure, so racks near fan walls or air handlers can pull hot air back through rack rails even when total supply exceeds total demand.
- A slab design has no way to modulate airflow by zone. A raised floor acts as a manifold, and tile open area can be adjusted to feed hot sections or to cut flow where racks are missing.
- Model leakage, and model the case with one air handler off. The presenter says leakage through racks, rails and ceilings is always present, and that slab layouts lose control of cold air once it leaks.
- Keep rack rows well clear of high-speed horizontal air. The presenter suggests at least eight feet from a fan coil unit, but stresses that it depends on the design.
- The presenter’s rule of thumb is about 100 cubic feet per minute (CFM) per kilowatt for newer servers, with older servers needing more. The presenter cautions that server fan controls vary and that this is a minimum for the heat transfer.
- The choice is framed as capital cost against operating cost: a slab design avoids the floor cost once, while the extra airflow or lower supply temperature needed to cover leakage is paid every day.